Analysis of common problems at fire acceptance site – fire door 1

Analysis of common problems at fire acceptance site - fire door 1

Acceptance items:Fire separation

Analysis of common problems at fire acceptance site - fire door 1

On-site problem description 1:

The fire door is not equipped with a door closer, and the double fire door is not equipped with a sequencer.

When the normally open fire door is a sub-door, there is no door closer on the sub-door.

Relevant specification requirements:

\”Code for Fire Protection Design of Buildings\” GB50016-2014 (2018 Edition):

6.5.1 The setting of fire doors should comply with the following regulations:

3. Except for tube well access doors and residential doors, fire doors should have a self-closing function.

\”Code for Construction and Acceptance of Fireproof Roller Shutters, Fireproof Doors, and Fireproof Windows\” GB50877—2014:

5.3.2 Normally closed fire doors should be equipped with door closers, and double-leaf and multi-leaf fire doors should be equipped with sequencers.

Analysis of common problems at fire acceptance site - fire door 1

Onsite problem description 2:

The evacuation doors in some parts are not equipped with Class A fire doors, such as the doors of the smoke prevention and exhaust machine room opening into the building, the doors of the evacuation aisles in the fire protection zone, Doors in underground garages opening to residential evacuation stairwells, doors on firewalls, etc.

The civil air defense area is adjacent to the fire protection zone. Only civil air defense doors are seen, and no Class A fire doors are installed.

Relevant specification requirements:

\”General Specifications for Building Fire Protection\” GB55037—2022:

6.4.2 Doors in the following locations should be Class A fire doors:

1. Doors set on the fire wall and doors set on the fire zone for evacuation corridors;

2. Set up a fire partition wall with a fire resistance limit of not less than 3.00hdoor;

3. Elevator room, The door connecting the evacuation stairwell to the garage;

4. Indoor doors opening to the front room of the evacuation corridor and evacuation doors in the evacuation room;

5. Doors leading from the warehouse to evacuation walkways or evacuation stairwells in multi-story Category B warehouses and underground, semi-underground and multi- and high-rise Category C warehouses.

6.4.5 Civilian air defense projects in daily use The fire resistance of protective doors, protective airtight doors, and airtight doors that replace Class A fire doors should not be lower than the requirements of Class A fire doors, and should not be used for evacuation exits in commonly used public places.

\”Code for Fire Protection Design of Buildings\” GB50016—2014 (2018 edition):

6.2.7 The doors of ventilation, air conditioning machine rooms and power transformation and distribution rooms that open into the building should use Class A fire doors, and the fire control room and other equipment rooms open to the doors in the building. Doors should be Class B fire doors.

\”Technical Specifications for Fire Water Supply and Fire Hydrant Systems\” GB50974—2014:

5.5.12 The fire pump room shall comply with the following requirements:

3. The fire pump room attached to the building should be separated from other parts by partition walls with a fire resistance rating of not less than 2.00h and floors of 1.50h. Its evacuation door should lead directly to the safety exit and open Doors to evacuation corridors should be Class A fire doors

\”Code for Fire Protection Design of Garages, Repair Garages and Parking Lots\” GB50067-2014:

6.0.7 For underground garages and semi-underground garages connected to residential basements, evacuation stairs in the residential part can be used for personnel evacuation; when it is not possible to directly enter the evacuation stairwell in the residential part, an evacuation staircase should be installed between the garage and the residential part. The connecting aisles should be separated by fire-resistant partition walls, and the doors of the garage opening to the aisles should be Class A fire-resistant doors

Analysis of common problems at fire acceptance site - fire door 1

On-site problem description 3:

The underground storage room does not use Class B fire doors;

The public kitchen in a public building is not separated from other parts as required by regulations.

Related specification requirements:

\”Code for Fire Protection Design of Buildings\” GB50016-2014 (2018 Edition):

6.2.3 The following parts of the building should be separated from other parts by fire partition walls with a fire resistance rating of not less than 2.00h. Doors and windows on the wall should be Class B fire doors and windows. If there are difficulties, fire shutters can be used, but Shall comply with the provisions of Article 6.5.3 of this specification:

4. Affiliated warehouses in civil buildings and auxiliary rooms behind theaters;

5. In addition to kitchens in residential buildings, public kitchens in dormitories and apartment buildings and kitchens in other buildings;

Analysis of common problems at fire acceptance site - fire door 1

The picture comes from the Internet. If there is any infringement, please contact us to delete it.

Message at the end of the article:

Good-looking skins are the same, but interesting souls Pick one out of a million.

@binmayedu (firefighting) is with you, let’s be interesting together!

本站内容及图片来自网络,版权归原作者所有,内容仅供读者参考,不承担相关法律责任,如有侵犯请联系我们:609448834

Like (0)
华夏门网的头像华夏门网
Previous 2024年12月25日
Next 2024年12月25日

相关推荐

  • 一家人去看房装修!4岁女儿在父亲眼皮底下 被400斤防火门砸死!

    来源 | 都市现场综合陕西都市青春频道 转载请注明全部来源 吴先生一家人原本去看房准备装修,然而4岁的女儿却在屋内发生了意外。 吴先生说,他孩子从事发地过的时候,突然震动,也不知道是拉着了啥,孩子一下被防火门拍死了。 这一幕就发生在4月21号,雅居乐湖居笔记小区内,吴先生说,他在小区6号楼购买了一间二手房,当天是前来装修开工。 吴先生告诉记者,孩子从那过的时…

    防火门 2023年10月19日
    50
  • 【微分享】疏散走道大于20m增设防火门,可以取消排烟设施吗?

    【重磅推出】“散装顾问”服务 编辑 机电人脉 《建筑设计防火规范》GB50016-2014 第8.5.3条规定:建筑内长度大于20m的疏散走道应设置排烟设施。 有的项目在遇到长度大于20m的疏散走道时,为了规避在走道设置排烟措施,会在疏散走道的中间设一道防火门,将疏散走道分为两段,每段的疏散走道长度均不大于20m。 这样是否疏散走道就不用设置排烟设施了呢?并…

    防火门 2023年10月23日
    1040
  • 甲级防火门

    甲级防火门 防火门是指能够在一定时间内承受火灾高温及烟气侵袭,起到隔热、隔离、隔烟的作用,阻止火势蔓延的门。它是建筑物消防设施的一部分,作为建筑物的安全防范措施之一。 防火门的主要作用包括: 1. 防止火势蔓延:采用防火材料和特殊结构设计,能够承受高温和烟气侵袭,起到隔热、隔离、隔烟的作用,阻止火势蔓延。 2. 保护人员安全:能有效隔离火势和烟气,延长人员撤…

    防火门 2024年4月29日
    40
  • 绷紧安全弦 筑牢生命线丨防火门开关有讲究

    □本报记者 黄岱昕 防火门是最常见的楼宇消防设施,可以在关键时刻阻止火势和烟雾蔓延。“防火门类型不同,用法也不同。”洛阳市消防救援支队防火监督科一级指挥员马睿龙说。 近日,记者跟随洛阳市消防救援支队工作人员,到该市洛龙区的大型商场、居民小区,实地探访防火门的设置以及消防通道安全保畅情况。 “商场一楼客流量大,所以需要设置这样的常开式防火门。”马睿龙指着一处安…

    防火门 2024年6月20日
    150
  • ​2023年上海市嘉定区防火窗产品质量监督抽查结果

    2023年嘉定区防火窗产品质量监督抽查结果 近期,嘉定区市场监督管理局对本区企业生产、销售的消防产品质量进行了监督抽查。本次抽查了2批次产品,经检验,全部合格。 2023年嘉定区防火窗产品质量监督抽查合格产品 序号 抽查产品 型号规格 受检企业 1 钢质隔热防火窗 GFC 0608-D-A1.00(乙级) 上海加汇消防安全设备工程有限公司 2 钢质隔热防火窗…

    防火门 2024年3月8日
    60

联系我们

400-800-8888

在线咨询: QQ交谈

邮件:[email protected]

工作时间:周一至周五,9:30-18:30,节假日休息

关注微信