Analysis of common problems at fire acceptance site – fire door 1

Analysis of common problems at fire acceptance site - fire door 1

Acceptance items:Fire separation

Analysis of common problems at fire acceptance site - fire door 1

On-site problem description 1:

The fire door is not equipped with a door closer, and the double fire door is not equipped with a sequencer.

When the normally open fire door is a sub-door, there is no door closer on the sub-door.

Relevant specification requirements:

\”Code for Fire Protection Design of Buildings\” GB50016-2014 (2018 Edition):

6.5.1 The setting of fire doors should comply with the following regulations:

3. Except for tube well access doors and residential doors, fire doors should have a self-closing function.

\”Code for Construction and Acceptance of Fireproof Roller Shutters, Fireproof Doors, and Fireproof Windows\” GB50877—2014:

5.3.2 Normally closed fire doors should be equipped with door closers, and double-leaf and multi-leaf fire doors should be equipped with sequencers.

Analysis of common problems at fire acceptance site - fire door 1

Onsite problem description 2:

The evacuation doors in some parts are not equipped with Class A fire doors, such as the doors of the smoke prevention and exhaust machine room opening into the building, the doors of the evacuation aisles in the fire protection zone, Doors in underground garages opening to residential evacuation stairwells, doors on firewalls, etc.

The civil air defense area is adjacent to the fire protection zone. Only civil air defense doors are seen, and no Class A fire doors are installed.

Relevant specification requirements:

\”General Specifications for Building Fire Protection\” GB55037—2022:

6.4.2 Doors in the following locations should be Class A fire doors:

1. Doors set on the fire wall and doors set on the fire zone for evacuation corridors;

2. Set up a fire partition wall with a fire resistance limit of not less than 3.00hdoor;

3. Elevator room, The door connecting the evacuation stairwell to the garage;

4. Indoor doors opening to the front room of the evacuation corridor and evacuation doors in the evacuation room;

5. Doors leading from the warehouse to evacuation walkways or evacuation stairwells in multi-story Category B warehouses and underground, semi-underground and multi- and high-rise Category C warehouses.

6.4.5 Civilian air defense projects in daily use The fire resistance of protective doors, protective airtight doors, and airtight doors that replace Class A fire doors should not be lower than the requirements of Class A fire doors, and should not be used for evacuation exits in commonly used public places.

\”Code for Fire Protection Design of Buildings\” GB50016—2014 (2018 edition):

6.2.7 The doors of ventilation, air conditioning machine rooms and power transformation and distribution rooms that open into the building should use Class A fire doors, and the fire control room and other equipment rooms open to the doors in the building. Doors should be Class B fire doors.

\”Technical Specifications for Fire Water Supply and Fire Hydrant Systems\” GB50974—2014:

5.5.12 The fire pump room shall comply with the following requirements:

3. The fire pump room attached to the building should be separated from other parts by partition walls with a fire resistance rating of not less than 2.00h and floors of 1.50h. Its evacuation door should lead directly to the safety exit and open Doors to evacuation corridors should be Class A fire doors

\”Code for Fire Protection Design of Garages, Repair Garages and Parking Lots\” GB50067-2014:

6.0.7 For underground garages and semi-underground garages connected to residential basements, evacuation stairs in the residential part can be used for personnel evacuation; when it is not possible to directly enter the evacuation stairwell in the residential part, an evacuation staircase should be installed between the garage and the residential part. The connecting aisles should be separated by fire-resistant partition walls, and the doors of the garage opening to the aisles should be Class A fire-resistant doors

Analysis of common problems at fire acceptance site - fire door 1

On-site problem description 3:

The underground storage room does not use Class B fire doors;

The public kitchen in a public building is not separated from other parts as required by regulations.

Related specification requirements:

\”Code for Fire Protection Design of Buildings\” GB50016-2014 (2018 Edition):

6.2.3 The following parts of the building should be separated from other parts by fire partition walls with a fire resistance rating of not less than 2.00h. Doors and windows on the wall should be Class B fire doors and windows. If there are difficulties, fire shutters can be used, but Shall comply with the provisions of Article 6.5.3 of this specification:

4. Affiliated warehouses in civil buildings and auxiliary rooms behind theaters;

5. In addition to kitchens in residential buildings, public kitchens in dormitories and apartment buildings and kitchens in other buildings;

Analysis of common problems at fire acceptance site - fire door 1

The picture comes from the Internet. If there is any infringement, please contact us to delete it.

Message at the end of the article:

Good-looking skins are the same, but interesting souls Pick one out of a million.

@binmayedu (firefighting) is with you, let’s be interesting together!

本站内容及图片来自网络,版权归原作者所有,内容仅供读者参考,不承担相关法律责任,如有侵犯请联系我们:609448834

(0)
华夏门网's avatar华夏门网
上一篇 2024年12月25日 09:19:15
下一篇 2024年12月25日 09:36:46

相关推荐

  • 消防设施操作员防火门系统维修

    防火门监控器应具备显示功能、控制功能、反馈功能、故障报警控制、信息记录、查询与上传功能、自检功能、备用电源功能和主、备电源转换功能。 常开式防火门无法正常关闭的原因有:(1)电磁释放器无法消磁。(2)电动闭门器滑槽内锁舌过紧或位置不当致防火门开启角度过大。(3)闭门器损坏。(4)模块损坏或无联动公式。(5)防火门监控器发生故障。(6)闭门器、连杆安装角度不正…

    防火门 2024年2月27日
    2380
  • 洋浦一小区多处防火门被拆 消防责令物业尽快恢复

    商报全媒体讯(椰网/海拔新闻记者 李兴民 通讯员 李京莹 摄影报道)近日,洋浦经济开发区消防救援支队接群众举报称,某小区住宅楼存在防火门被拆除的情况。接到举报后,该支队消防监督员立即前往现场核查发现,该小区住宅楼多处防火门被拆除。 9月8日,洋浦经济开发区消防救援支队接到居民举报投诉称,某小区某栋住宅楼14层的防火门被拆除,存在消防安全隐患。接到举报信息后,…

    防火门 2023年10月3日
    340
  • 常閉式防火門可以隨意開啟嗎?

    常閉式防火門必須常閉,惡意破壞違法。在發生火災時,無論是向下逃生還是向上通過屋頂平臺疏散,樓梯間都不能有任何煙氣和火焰,這就需要常閉式防火門發揮作用。如果常閉式防火門被開啟,濃煙和火勢就會擴散至樓梯間,從而快速蔓延至整棟樓,十分危險。 防火門的隔熱防火時間都是一樣的嗎? 不一樣。防火門按照耐火性能,可以分為:隔熱防火門(A類)、部分隔熱防火門(B類)和非隔熱…

    防火门 2024年9月4日
    900
  • 讓我看看,你傢小區的防火門,是不是真能防火?

    3月12日~13日,鄂州市消防救援支隊聯合市場監管部門(質監、工商)組成聯合檢查組,深入星都匯KTV、和風朗苑小區和宏泰鑫華庭小區等建設工程開展消防產品專項檢查。 執法人員嚴格按照《中華人民共和國產品質量法》、《消防產品現場檢查判定規則》等法律法規,采取查閱產品檢測報告、對比生產廠傢資質、現場抽樣檢測等方式,對小區防火門、滅火器、應急燈具、消防水帶、消防軟管…

    防火门 2024年8月25日
    140
  • 防火门检查常用条款

    一、《建筑设计防火规范(2018年版)》(GB50016-2014) 6.5.4防火门的设置应符合下列规定: 1设置在建筑内经常有人通行处的防火门宜采用常开防火门。常开防火门应能在火灾时自行关闭,并应具有信号反馈的功能。 2除允许设置常开防火门的位置外,其他位置的防火门均应采用常闭防火门。常闭防火门应在其明显位置设置“保持防火门关闭”等提示标识。 3除管进检…

    防火门 2023年11月28日
    810

联系我们

400-800-8888

在线咨询: QQ交谈

邮件:[email protected]

工作时间:周一至周五,9:30-18:30,节假日休息

关注微信