Analysis of common problems at fire acceptance site – fire door 1

Analysis of common problems at fire acceptance site - fire door 1

Acceptance items:Fire separation

Analysis of common problems at fire acceptance site - fire door 1

On-site problem description 1:

The fire door is not equipped with a door closer, and the double fire door is not equipped with a sequencer.

When the normally open fire door is a sub-door, there is no door closer on the sub-door.

Relevant specification requirements:

\”Code for Fire Protection Design of Buildings\” GB50016-2014 (2018 Edition):

6.5.1 The setting of fire doors should comply with the following regulations:

3. Except for tube well access doors and residential doors, fire doors should have a self-closing function.

\”Code for Construction and Acceptance of Fireproof Roller Shutters, Fireproof Doors, and Fireproof Windows\” GB50877—2014:

5.3.2 Normally closed fire doors should be equipped with door closers, and double-leaf and multi-leaf fire doors should be equipped with sequencers.

Analysis of common problems at fire acceptance site - fire door 1

Onsite problem description 2:

The evacuation doors in some parts are not equipped with Class A fire doors, such as the doors of the smoke prevention and exhaust machine room opening into the building, the doors of the evacuation aisles in the fire protection zone, Doors in underground garages opening to residential evacuation stairwells, doors on firewalls, etc.

The civil air defense area is adjacent to the fire protection zone. Only civil air defense doors are seen, and no Class A fire doors are installed.

Relevant specification requirements:

\”General Specifications for Building Fire Protection\” GB55037—2022:

6.4.2 Doors in the following locations should be Class A fire doors:

1. Doors set on the fire wall and doors set on the fire zone for evacuation corridors;

2. Set up a fire partition wall with a fire resistance limit of not less than 3.00hdoor;

3. Elevator room, The door connecting the evacuation stairwell to the garage;

4. Indoor doors opening to the front room of the evacuation corridor and evacuation doors in the evacuation room;

5. Doors leading from the warehouse to evacuation walkways or evacuation stairwells in multi-story Category B warehouses and underground, semi-underground and multi- and high-rise Category C warehouses.

6.4.5 Civilian air defense projects in daily use The fire resistance of protective doors, protective airtight doors, and airtight doors that replace Class A fire doors should not be lower than the requirements of Class A fire doors, and should not be used for evacuation exits in commonly used public places.

\”Code for Fire Protection Design of Buildings\” GB50016—2014 (2018 edition):

6.2.7 The doors of ventilation, air conditioning machine rooms and power transformation and distribution rooms that open into the building should use Class A fire doors, and the fire control room and other equipment rooms open to the doors in the building. Doors should be Class B fire doors.

\”Technical Specifications for Fire Water Supply and Fire Hydrant Systems\” GB50974—2014:

5.5.12 The fire pump room shall comply with the following requirements:

3. The fire pump room attached to the building should be separated from other parts by partition walls with a fire resistance rating of not less than 2.00h and floors of 1.50h. Its evacuation door should lead directly to the safety exit and open Doors to evacuation corridors should be Class A fire doors

\”Code for Fire Protection Design of Garages, Repair Garages and Parking Lots\” GB50067-2014:

6.0.7 For underground garages and semi-underground garages connected to residential basements, evacuation stairs in the residential part can be used for personnel evacuation; when it is not possible to directly enter the evacuation stairwell in the residential part, an evacuation staircase should be installed between the garage and the residential part. The connecting aisles should be separated by fire-resistant partition walls, and the doors of the garage opening to the aisles should be Class A fire-resistant doors

Analysis of common problems at fire acceptance site - fire door 1

On-site problem description 3:

The underground storage room does not use Class B fire doors;

The public kitchen in a public building is not separated from other parts as required by regulations.

Related specification requirements:

\”Code for Fire Protection Design of Buildings\” GB50016-2014 (2018 Edition):

6.2.3 The following parts of the building should be separated from other parts by fire partition walls with a fire resistance rating of not less than 2.00h. Doors and windows on the wall should be Class B fire doors and windows. If there are difficulties, fire shutters can be used, but Shall comply with the provisions of Article 6.5.3 of this specification:

4. Affiliated warehouses in civil buildings and auxiliary rooms behind theaters;

5. In addition to kitchens in residential buildings, public kitchens in dormitories and apartment buildings and kitchens in other buildings;

Analysis of common problems at fire acceptance site - fire door 1

The picture comes from the Internet. If there is any infringement, please contact us to delete it.

Message at the end of the article:

Good-looking skins are the same, but interesting souls Pick one out of a million.

@binmayedu (firefighting) is with you, let’s be interesting together!

本站内容及图片来自网络,版权归原作者所有,内容仅供读者参考,不承担相关法律责任,如有侵犯请联系我们:609448834

(0)
华夏门网's avatar华夏门网
上一篇 2024年12月25日 09:19:15
下一篇 2024年12月25日 09:36:46

相关推荐

  • 不合格防火门火灾隐患巨大,专家解读如何判断防火门质量

    常闭式防火门,是指那些在建筑中为防止火灾发生后烟气扩散,需要始终保持关闭的安全门,是高层建筑消防安全的重要防线。然而记者近日在多个城市的商场、高层住宅等场所跟随消防监督员检查时发现,一些地方安装的常闭式防火门存在产品质量问题,有的甚至是不合格产品。 在江西德兴市,记者跟随检查人员随机走访了一家新开业的宾馆,该宾馆新安装的防火门,门扇就出现了开启不灵活的卡阻现…

    防火门 2024年3月22日
    170
  • 山東凱華門業取得用於防火門生產的熱壓膠合設備專利,提升防火門板加工的效率

    金融界2024年11月16日消息,國傢知識產權局信息顯示,山東凱華門業有限公司取得一項名為“一種用於防火門生產的熱壓膠合設備”的專利,授權公告號 CN 222003804 U,申請日期為2024年3月。 專利摘要顯示,本實用新型涉及防火門加工技術領域,尤其涉及一種用於防火門生產的熱壓膠合設備,包括加工臺、上膠組件、控制端、輸送臺、壓合板,加工臺上分別設有控制…

    防火门 2024年11月22日
    90
  • 防火门及配件检测标准汇总

    防火门及配件检测哪些项目?检测周期多久呢?检测报告如何办理?测试方法有哪些?做检测,找百检! 检测项目: 尺寸偏差、灵活性(门扇开启力)、钢材(材料厚度)、防火合页(铰链)(耐火性能))、防火插销(耐火性能)、防火锁(耐火性能)、防火顺序器(耐火性能)、材料性能、耐火性能(防火锁)、配件性能、尺寸*限偏差、形位公差、可靠性、门扇质量、外观质量、灵活性、配合公…

    防火门 2024年5月2日
    110
  • 江蘇省蘇州市發佈2024年防火門產品質量市級監督抽查情況(第57期)

    中國質量新聞網訊 近日,江蘇省蘇州市市場監督管理局發佈2024年防火門產品質量市級監督抽查情況(第57期)。本次抽查16批次產品,合格16批次,合格率為100%。 2024年3-6月,蘇州市市場監督管理局委托常州市建築科學研究院集團股份有限公司對防火門產品質量實施瞭市級監督抽查。本次抽檢任務計劃抽取16批次,實際抽到16批次,均在生產企業中抽取。 防火門產品…

    防火门 2024年10月24日
    180
  • 隐患排查与治理依据— 防火门1

    隐患排查与治理依据— 防火门1 1.隐患描述:常闭防火门无自行关闭功能,可能导致防火门处于开启状态,火灾发生时,烟热可通过防火门蔓延,存在火势快速扩大的风险。。 隐患分类:消防安全 隐患性质:一般隐患 隐患依据:GB 50016-2014 建筑设计防火规范 6.5.1 整改建议:常闭防火门应安装闭门器等自行关闭装置。 2.隐患描述:常闭防火门自行关闭功能失效…

    防火门 2024年3月19日