Analysis of common problems at fire acceptance site – fire door 1

Analysis of common problems at fire acceptance site - fire door 1

Acceptance items:Fire separation

Analysis of common problems at fire acceptance site - fire door 1

On-site problem description 1:

The fire door is not equipped with a door closer, and the double fire door is not equipped with a sequencer.

When the normally open fire door is a sub-door, there is no door closer on the sub-door.

Relevant specification requirements:

\”Code for Fire Protection Design of Buildings\” GB50016-2014 (2018 Edition):

6.5.1 The setting of fire doors should comply with the following regulations:

3. Except for tube well access doors and residential doors, fire doors should have a self-closing function.

\”Code for Construction and Acceptance of Fireproof Roller Shutters, Fireproof Doors, and Fireproof Windows\” GB50877—2014:

5.3.2 Normally closed fire doors should be equipped with door closers, and double-leaf and multi-leaf fire doors should be equipped with sequencers.

Analysis of common problems at fire acceptance site - fire door 1

Onsite problem description 2:

The evacuation doors in some parts are not equipped with Class A fire doors, such as the doors of the smoke prevention and exhaust machine room opening into the building, the doors of the evacuation aisles in the fire protection zone, Doors in underground garages opening to residential evacuation stairwells, doors on firewalls, etc.

The civil air defense area is adjacent to the fire protection zone. Only civil air defense doors are seen, and no Class A fire doors are installed.

Relevant specification requirements:

\”General Specifications for Building Fire Protection\” GB55037—2022:

6.4.2 Doors in the following locations should be Class A fire doors:

1. Doors set on the fire wall and doors set on the fire zone for evacuation corridors;

2. Set up a fire partition wall with a fire resistance limit of not less than 3.00hdoor;

3. Elevator room, The door connecting the evacuation stairwell to the garage;

4. Indoor doors opening to the front room of the evacuation corridor and evacuation doors in the evacuation room;

5. Doors leading from the warehouse to evacuation walkways or evacuation stairwells in multi-story Category B warehouses and underground, semi-underground and multi- and high-rise Category C warehouses.

6.4.5 Civilian air defense projects in daily use The fire resistance of protective doors, protective airtight doors, and airtight doors that replace Class A fire doors should not be lower than the requirements of Class A fire doors, and should not be used for evacuation exits in commonly used public places.

\”Code for Fire Protection Design of Buildings\” GB50016—2014 (2018 edition):

6.2.7 The doors of ventilation, air conditioning machine rooms and power transformation and distribution rooms that open into the building should use Class A fire doors, and the fire control room and other equipment rooms open to the doors in the building. Doors should be Class B fire doors.

\”Technical Specifications for Fire Water Supply and Fire Hydrant Systems\” GB50974—2014:

5.5.12 The fire pump room shall comply with the following requirements:

3. The fire pump room attached to the building should be separated from other parts by partition walls with a fire resistance rating of not less than 2.00h and floors of 1.50h. Its evacuation door should lead directly to the safety exit and open Doors to evacuation corridors should be Class A fire doors

\”Code for Fire Protection Design of Garages, Repair Garages and Parking Lots\” GB50067-2014:

6.0.7 For underground garages and semi-underground garages connected to residential basements, evacuation stairs in the residential part can be used for personnel evacuation; when it is not possible to directly enter the evacuation stairwell in the residential part, an evacuation staircase should be installed between the garage and the residential part. The connecting aisles should be separated by fire-resistant partition walls, and the doors of the garage opening to the aisles should be Class A fire-resistant doors

Analysis of common problems at fire acceptance site - fire door 1

On-site problem description 3:

The underground storage room does not use Class B fire doors;

The public kitchen in a public building is not separated from other parts as required by regulations.

Related specification requirements:

\”Code for Fire Protection Design of Buildings\” GB50016-2014 (2018 Edition):

6.2.3 The following parts of the building should be separated from other parts by fire partition walls with a fire resistance rating of not less than 2.00h. Doors and windows on the wall should be Class B fire doors and windows. If there are difficulties, fire shutters can be used, but Shall comply with the provisions of Article 6.5.3 of this specification:

4. Affiliated warehouses in civil buildings and auxiliary rooms behind theaters;

5. In addition to kitchens in residential buildings, public kitchens in dormitories and apartment buildings and kitchens in other buildings;

Analysis of common problems at fire acceptance site - fire door 1

The picture comes from the Internet. If there is any infringement, please contact us to delete it.

Message at the end of the article:

Good-looking skins are the same, but interesting souls Pick one out of a million.

@binmayedu (firefighting) is with you, let’s be interesting together!

本站内容及图片来自网络,版权归原作者所有,内容仅供读者参考,不承担相关法律责任,如有侵犯请联系我们:609448834

(0)
华夏门网's avatar华夏门网
上一篇 2024年12月25日 09:19:15
下一篇 2024年12月25日 09:36:46

相关推荐

  • 火灾中的生命之门——防火门

    近年来 城市的高层建筑越来越多 给人们的生活和工作带来了诸多便利 然而 我们也不得不面对高层建筑一旦失火所带来的巨大威胁和风险 据中国消防统计,今年1至10月,全国共接报火灾74.5万起,死亡1381人,受伤2063人,已核直接财产损失61.5亿元,与去年同期相比,起数和伤人数分别上升2.5%和6.5%,亡人数和损失分别下降13.2%和9.7%。 为什么高层…

    防火门 2023年12月8日
    290
  • 河北省市场监督管理局抽查防火门:不合格样品3批次

    据河北省市场监督管理局网站5月22日消息,为进一步加强河北省产品质量安全监管,切实维护消费者合法权益,该局采取购买样品方式,抽查检测手提式灭火器、防火门、电动自行车、蓄电池、防火涂料、火灾报警器、防爆灯具、发电机(起动机)、钢管脚手架扣件、建筑防水卷材、建筑用涂料、料理机、摩擦衬片、墙体保温材料、钢筋、人造板、电(水)热毯、化肥、床上用品、服装、鞋、贵金属饰…

    防火门 2024年5月23日
    150
  • 隐患排查与治理依据— 防火门2

    隐患排查与治理依据— 防火门2 1.隐患描述:现场设置的常闭防火门处于开启状态,火灾发生时,烟热可通过防火门蔓延,存在火势快速扩大的风险。。 隐患分类:消防安全 隐患性质:一般隐患 隐患依据:GB 50016-2014 建筑设计防火规范 6.5.1 整改建议:常闭防火门应处于常闭状态。 2.隐患描述:现场测试时,双扇防火门未能按正确顺序关闭,造成双扇防火门关…

    防火门 2024年3月20日
    270
  • 防火门生产流程

    防火门 防火门是指具有一定耐火性能的门,常用于防火隔断和逃生通 道。为了确保防火门的质量和性能达到相关国家标准,防火门的生产流程需要严格控制。 防火门生产流程 防火门的生产流程是关乎质量和安全的重要环节。防火门生产过程中需要通过精确的切割、冲压和焊接等工艺,将材料加工成合适尺寸和形状的门扇和门框。 第一步:下料 防火门的下料是制作防火门的重要环节,合理的下料…

    防火门 2024年1月19日
    2810
  • 这道门,今天你关了吗?(涨知识)

    防火门,到底是什么门 ❓❓❓ 如果单从名字上看 “防火门”这三个字让人安全感满满 似乎有了这道门 发生火灾就再也不怕了 那么 防火门究竟有多重要? 防火门的 “前世今生” 究竟什么是防火门? 防火门是指在一定时间内能满足耐火稳定性、完整性和隔热性要求的门。防火门除具有普通门的作用外,更具有阻止火势蔓延和烟气扩散的作用,为疏散争取时间。 防火门按照耐火性能,可…

    防火门 2023年11月2日
    60

联系我们

400-800-8888

在线咨询: QQ交谈

邮件:[email protected]

工作时间:周一至周五,9:30-18:30,节假日休息

关注微信