Reprint–Several common faults and solutions for electric doors

Source: Zhu Hongming Zhongtian Iron and Steel Thermal Power Plant

Electric doors are common equipment in industrial systems. They cooperate with DCS and PLC and are easy and flexible to operate. However, there will also be faults of one kind or another. Here are some of the more common faults. Analyze it and find a simple way to deal with it.

1. The electric door cannot be opened or closed

Reprint--Several common faults and solutions for electric doors

Reprint--Several common faults and solutions for electric doors

The electric door cannot be opened or closed. First, go to the electric door control cabinet, whether it is integrated or a separate operation cabinet, and check whether the A1B control power supply has power. On the one hand, it is a power trip and cannot be checked. Power supply, on the other hand, the torque switch of the electric door acts, or the torque switch is broken, the A25 yellow indicator light will light up. When this happens, turn on the power supply A12 or turn off the power supply A42. If the power is not measured, readjust the torque switch and select the appropriate one. forceTorque, under normal circumstances, the opening torque is 1-1.5 times larger than the closing torque, just release the torque switch. If the torque switch is broken, replace it and use a multimeter to measure it.

Secondly, the motor is damaged. At this time, it is necessary to cut off the power and use a multimeter to measure whether the three-phase resistance of the motor is balanced. If the surface of the motor is hot, the three-phase resistance has a large deviation, or even If only two equal conditions can be measured, it is judged that the motor is damaged and must Replace the motor with the same model. After replacing the motor, you must determine that the phase is the same as before, so that the motor replacement is successful. Note that when determining the motor phase, you must manually turn the electric door to the middle position before it can be opened or closed to avoid The motor is damaged again, the electric door is over-opened or closed, etc.

2. The electric head is turning when opening and closing, but the valve does not move

Reprint--Several common faults and solutions for electric doors

This situation is relatively rare, but generally the connection between the electric head and the valve is damaged. It is usually made of copper material and cannot rotate for a long time, or there is a problem with the original installation. The wire mouth is damaged. When this happens, disconnect the electric head from the valve and operate the electric head alone. As long as the electric head rotates normally, it can be basically concluded that it is a flexible problem, and it only needs to be replaced.

3. The electric door cannot be operated in DCS, but can be operated locally

Reprint--Several common faults and solutions for electric doors

This problem has two aspects. On the one hand, it is a relatively simple problem. The problem that novices easily encounter is that there is a transfer switch on the local operation cabinet. The switch has two directions to choose from, remote and local. Turn the switch to the remote position and you can operate in the DCS. , on the other hand, it is more complicated. There may be a problem with the DCS card. In this case, check whether the card channel is intact and whether there is a problem with the output relay. If there is a problem with the card, replace the card. If there is a problem with the relay, replace the relay until Problem solved.

There are also some more complex and cumbersome problems, such as damage to the internal transmission mechanism of the electric door, etc., which I will not analyze one by one. When you encounter these problems that cannot be solved, choose to replace the electric head with a new one to ensure The electric door operates normally.

If there is anything wrong with the above, please correct me and forgive me!

本站内容及图片来自网络,版权归原作者所有,内容仅供读者参考,不承担相关法律责任,如有侵犯请联系我们:609448834

(0)
华夏门网's avatar华夏门网
上一篇 2024年12月15日 10:57:26
下一篇 2024年12月15日 11:04:23

相关推荐

  • Ningbo Tianan obtained a patent for a low-voltage switch cabinet electric door

    According to news from the financial industry on January 15, 2025, information from the State Intellectual Property Office shows that Ningbo Tianan (Group) Co., Ltd. has obtained a…

    电动门 2025年1月16日
    80
  • What electric door scenes can the Giant Optical and Electrical Door integrated control system be used for?

    What electric doors can the Giant Optical Electrical Door Centralized Control System be used for? Juguang Smart Door Control will use this article to share the electric doors that …

    电动门 2025年2月27日
    210
  • EMG电动门调整方法!

    欢迎关注“热控圈 ” 传播热控知识,分享技术精华! EMG电动门调整方法 1、不带液晶屏的EMG电动门调整方法 就地操作开关按钮图 首先设定进入learn 模式(调试模式) 先按下LT按钮并保持,同时把S1拔钮开关移至Learn位置(注意顺序不能反,一定要先按LT再S1拔钮,否则无效)。 大约10秒以后,就地指示灯(开、关两只指示灯)同时开始闪亮烁。这表示执…

    电动门 2023年11月26日
    700
  • 工業園區廠房電動門安全氣囊的適用范圍解析

    工業園區廠房電動門安全氣囊的適用范圍解析 在工業園區的廠房電動門安全防護領域,安全氣囊作為一種重要的安全保護裝置,其作用不可忽視。然而,並非所有的工業門都適合安裝安全氣囊,這需要綜合多方面因素進行考量,其中主要包括工業門的寬度限制、環境要求以及特殊門體類型等。 一、寬度限制對安全氣囊適用范圍的影響 (一)適宜安裝安全氣囊的門寬范圍 一般來說,對於寬度在一定范…

    电动门 2024年10月27日
    130
  • 阿維塔11的智能感應電動門體驗,上下車更輕松?

    不知道大傢是否和我有相同或者相似的經歷?大傢在購買一輛車的時候對電動車門有沒有要求,接下來把我的經歷分享給大傢。 今天我駕駛著這輛阿維塔11出行,到瞭停車場以後發現這個車位比較窄,我就在車內糾結開門會不會蹭到旁邊的車門,而且開瞭門之後這個空間我到底能不能下瞭車,就在我特別焦慮的時候,想到當時購買這輛阿維塔11的時候,銷售小哥告訴我這輛車配備有智能感應電動門。…

    电动门 2024年9月11日
    750

联系我们

400-800-8888

在线咨询: QQ交谈

邮件:[email protected]

工作时间:周一至周五,9:30-18:30,节假日休息

关注微信