Fire door deformation, alarm host failure… Reporters followed the fire department to continuously expose a number of fire hazards

In accordance with the work requirements of the fire safety \”big investigation, big exposure, big rectification\” action, the reporter followed the Chengdu fire expert team and continued to visit some crowded places in the High-tech Zone, Dujiangyan City, Pidu District, and Xinjin District Undercover inspections were conducted, and a total of 8 public entertainment venues were inspected, and 32 fire hazards were found. The hidden hazards are now being exposed, and expert interpretations of some of the hazards are provided.

High-tech Zone

Catering venues: CapitaLand Tianfu, 6th Floor, No. 388 Tianren Road, Wuhou District, Chengdu

( 1) Many fire doors in this place were deformed and the fire door sequencer failed.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

Basis: This item violates the provisions of Article 16 of the Fire Protection Law of the People\’s Republic of China: Agencies, groups, enterprises, institutions and other units shall implement the following fire safety regulations Responsibilities: Configure fire-fighting facilities and equipment in accordance with national and industry standards, set fire safety signs, and organize regular inspections and maintenance to ensure they are intact and effective.

Expert interpretation: This place is a large commercial complex. There are many fire doors deformed and fire door sequencers malfunctioning in the place, including the kitchen and the fire doors leading to the stairwell.

(2) Many of the evacuation indicator lamps that maintain visual continuity in this place are faulty and partially blocked, and there are no signs under the fire shutters.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

(3) Tables and chairs are set up in front of an evacuation door in this place, and items stacked in the stairwells and evacuation passages affect safe evacuation.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

(4) Many air ducts and water pipes passing through fireproof partition walls in this place have not been fireproofed and sealed.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

(5) A lighting fixture on the stairwell floor of the site was faulty, and a safety exit sign lighting fixture was blocked by an air duct.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

Shopping mall: Suning Plaza City Outlets ( Tianfu Overpass Store), the first floor of No. 8, North Section of Tianfu Avenue, High-tech Zone, Chengdu

(1) There are many safety exit evacuation doors, stairwells, and evacuation corridors where items are piled up in front of the site. The impact of installing latches on the evacuation doors Evacuate safely

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

(2) The evacuation doors of many shops in this place cannot lead directly to the outdoor ground or evacuation stairwells, nor to evacuation aisles, and items are piled under the fire-proof roller shutters. , no flag set.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

Expert interpretation: Some businesses in this place Stores are equipped with fire-proof roller shutters and other parts to divide fire protection zones. Multiple store evacuation doors cannot lead directly to the outdoor ground or evacuation stairwells, nor do they lead to evacuation aisles. One or more stores must be passed to reach the safety exit. Stores exist Nested evacuation. The evacuation of people from indoor rooms should ensure that the risk is reduced step by step. When indoor rooms are set up in nested (sleeved) configurations, the internal rooms In the event of a fire, you must pass through another dangerous area to reach the evacuation aisle or safety exit, and there is a certain risk. The key is that if the external room catches fire, it will directly block the safe evacuation of the internal room.

(3) The door closers and sequencers of many fire doors in this place were faulty or missing, and one fire door in this place was replaced with an ordinary door.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

(4) The selection of many evacuation indicator lamps in this place is incorrect, and the installation direction of the evacuation indicator lamps is inconsistent with the actual evacuation plan.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

Dujiangyan City

1. Passenger Transport Center: Dujiangyan Passenger Transport Center, 1st Floor, No. 76, Yingbin Road, Dujiangyan City, Chengdu

(1) The number of fire extinguishers in the outbound passage of this site is insufficient, and the spacing between them is greater than the specification requirements.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

(2) The evacuation indicator lamp of the outbound passage of the site failed, and the power cord of the evacuation indicator lamp was not protected by a metal tube.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

(3) There are no safety exit sign lamps installed above the evacuation door in the entrance hall and exit entrance of this place, and there are hanging lights above the evacuation door at the entrance entrance. Installing locks affects safe evacuation.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

(4) E-bikes are parked in the outbound passage of this place.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

Expert Interpretation: This place is a multi-story public building, which is a densely populated place. Parking electric bicycles on the evacuation passage out of the station violates Article 7.8.2 of the \”Fire Safety Management of Densely Populated Places\” GB/T40248-2021 Article: Electrical fire safety management should meet the following requirements: Parking and charging of electric bicycles is strictly prohibited in crowded places.

2. Hotels: Huahai Hot Spring Hotel (Dujiangyan Scenic Area Branch), Guankou, Dujiangyan City, Chengdu. 2nd Floor, No. 12, No. 151, Upper Zoumahe East Road, Taiping Community

(1) The evacuation door from the corridor leading to the outer corridor of the place did not open in the evacuation direction.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

Expert interpretation: The evacuation door is a door set in each room in the building that directly leads to the evacuation corridor or a door on the safety exit. In order to avoid the panic and crowding of the crowd in the event of a fire, the evacuation door The door leaf cannot be opened, and the evacuation door is required to be opened in the evacuation direction. The place is located on the second floor of a multi-story public building. , there are two safety exits leading to the outer corridor, and the evacuation door of one of the safety exits leading to the outer corridor does not open in the evacuation direction.

(2) The electrical wiring between the linen in this place is not arranged in a standardized manner. and installation, the smoke detector was not installed at the top, and there were holes in the fireproof partition wall between the room and the corridor that were not fireproofed.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

(3) The fire alarm host of the place had a backup power failure, and a smoke detector reported a fire alarm.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

(4) The evacuation door leading to the stairwell in this place does not open in the evacuation direction. There is no safety exit sign lamp above the evacuation door. The above-ground and underground parts of the stairwell are connected, and the emergency lighting lamps in the stairwell are missing.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

Pidu District

Expressway Service Area: Ande Service Area (Rongchang Expressway (Chengdu direction), Chengdu Pidu District Chengguan Expressway Ande Service Area (Rongchang Expressway Chengdu direction)

(1) One of the evacuation indicator lamp hanging chains at the site was broken, and one of the smoke detectors The dust cover of the device was not removed in time and the sprinkler head was installed incorrectly.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

(2) Fire extinguishers and disinfectants in this place Fire hydrants were not regularly inspected.

Interpretation: This place is open to the public and is an indoor place for commercial operations. It is a crowded place. The fire hydrants and fire extinguishers in this place are not regularly inspected. This is a violation. \”Fire Protection Law of the People\’s Republic of China\” Tenth Article 6: Agencies, groups, enterprises, institutions and other units shall perform the following fire safety responsibilities: configure fire protection facilities and equipment in accordance with national standards and industry standards, set fire safety signs, and organize regular inspections and maintenance to ensure that they are intact and effective. /p>Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

(3) One of the safety exits in the place is locked.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

2. Nursing home: Yijin Nursing Home, No. 71, Shunhe East Street, Pidu District, Chengdu

(1) A storage room is provided in the enclosed stairwell of this place. p>Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

(2) The kitchen of this place is not completely separated from other parts by fireproof partition walls and fireproof doors and windows, and the evacuation door in the kitchen is locked.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

(3) Many smoke detectors in the place reported fire alarms, the alarm host had a large number of faults, and the fire-fighting equipment was not regularly inspected. Maintenance.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

Expert interpretation: This place is a multi-story public building with automatic fire alarm systems, fire hydrant systems, automatic sprinkler systems, etc. There are a large number of host failures and the fire-fighting equipment has not been regularly inspected. Maintenance will cause fire-fighting facilities to be unable to operate in the event of a fire, causing the fire to expand and spread.

(4) Some fire door closers and sequencers in this place are faulty, and some floor display lamps are not installed in the stairwell. No safety exit sign lights are installed above the evacuation door.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

Xinjin District

1. Hospital outpatient building: Xinjin District People\’s Hospital, No. 149 Wujin West Road, Xinjin District, Chengdu City Floor 1~2

(1) The evacuation door on the first floor of a stairwell in this place did not open in the evacuation direction, there were no safety exit sign lamps above many evacuation doors, and the door closers of some fire doors were missing.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

(2) There is no automatic fire extinguishing facility in the lobby on the first floor of this place.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

(三) Objects were piled in the stairwell and the evacuation door on the first floor of the place. An evacuation door was padlocked on the outside, causing the evacuation door to not open normally. Resting chairs were set up at the evacuation door to block the evacuation exit, and individual evacuation indicator lights were blocked.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

(4) A storage room is provided in an evacuation stairwell on the first floor of the place.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

2. Training institution: Xuri Dongsheng Education, No. 96 Wujin South Road, Xinjin District, Chengdu Bell Tower 3rd Floor

(1) There are no audible and visual alarms, manual alarm buttons and fire broadcasts in this place.

Expert interpretation: This place is equipped with an automatic fire alarm system and automatic fire alarm system. Sprinkler system, fire hydrant system, evacuation indication system, etc. The fire detector installed in the automatic fire alarm system is an automatic trigger alarm device, while the manual fire alarm button is a manual trigger alarm device. In the design, both automatic fire alarm systems should be equipped with fire alarm devices. Sound and light alarms are used to sound the alarm in the event of a fire. Its main purpose is to alert personnel in the event of a fire and warn personnel in a timely manner. Evacuation. When a fire occurs, everyone should be informed as soon as possible. At the same time, in order to avoid crowding at evacuation passages and exits due to mistimed evacuation, emergency broadcasts are required to be broadcast to the entire building at the same time after the fire is confirmed. The inspection found that the important components of the automatic fire alarm system were missing in the premises: audible and visual alarms, manual alarm buttons and fire broadcasts.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

(2) The fire door sequencer in this place is missing, and the setting of the latch affects safe evacuation.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

(3) The fire hydrant button in this place is missing, and the two fire hydrant valves are faulty and cannot be opened normally.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

(4) The positive pressure air supply vent louvers in the front room of the stairwell of this place were damaged, the normally closed air valve was not reset in time, and the emergency lighting fixtures in the stairwell were missing.

Fire door deformation, alarm host failure... Reporters followed the fire department to continuously expose a number of fire hazards

Basis: This item violates the provisions of Article 16 of the Fire Protection Law of the People\’s Republic of China: Agencies, regiments Entities, enterprises, institutions and other units shall perform the following fire safety responsibilities: configure fire protection facilities and equipment in accordance with national standards and industry standards, set fire safety signs, and organize regular inspections and maintenance to ensure they are intact and effective.

Chengdu. Daily Jinguan News Reporter Xu Songming Picture Xu Songming Chengdu Fire Protection Editor Liu Yang Editor Dai Aicen Reviewer Zhu Guangze Cao Yuyang

本站内容及图片来自网络,版权归原作者所有,内容仅供读者参考,不承担相关法律责任,如有侵犯请联系我们:609448834

(0)
华夏门网's avatar华夏门网
上一篇 2025年1月20日 09:44:49
下一篇 2025年1月20日 09:53:32

相关推荐

  • 俄罗斯防火门EAC认证-钢门-木门-消防门-防盗门认证

    俄罗斯防火门EAC认证-钢门-木门-消防门-防盗门认证 钢制防火门认证 防火门认证是对这些建筑产品的质量进行评估,证明产品符合安全标准和法律要求的过程。这种检查的结果是颁发合格证书。 防火认证是强制性程序吗? 1、在俄罗斯使用 PVC、铝和木铝制成的阳台门必须获得GOST-R声明(PP FR 第982号和 PP RF 第2425号)。 2、此外,俄罗斯防火门…

    防火门 2023年11月21日
    180
  • 漳州甲级防火门

    漳州甲级防火门:安全的 近年来,火灾频发已经成为一个性的问题,给人们的生命财产安全带来了巨大的威胁。 为了应对火灾的挑战,漳州甲级防火门应运而生,成为人们生命财产安全的。 漳州甲级防火门是一种在火灾中具有良好防火性能的门,它采用了的防火材料和的制造,通过对门体的特殊设计和处理,使其在火灾发生时能够有效地隔烟雾和火焰,延缓火势蔓延的速度,给人们争取了宝贵的逃生…

    防火门 2023年9月25日
    140
  • 锐亿科技取得一种方便观察的钢制防火门专利,通过特殊结构方便使用者进行观察

    金融界2024年5月30日消息,据国家知识产权局公告,浙江锐亿智能科技股份有限公司取得一项名为“一种方便观察的钢制防火门“,授权公告号CN221032283U,申请日期为2023年10月。 专利摘要显示,本实用新型公开了一种方便观察的钢制防火门,包括门框,所述门框的内侧对称设有防火门本体,所述防火门本体的正面设有探孔,所述探孔的内侧固定安装有玻璃板,所述探孔…

    防火门 2024年5月30日
    150
  • 防火木门好不好?常州装修网分析防火木门价格优势

    虽然现在室内门种类繁多,但还是有一些门让业主们对它的质量产生疑问。防火木门就是其中一种,从它的材质上看不禁让人产生疑惑,防火木门真的能防火吗?下面,常州装修网给大家说明防火木门价格及规范。 一、防火木门是什么? 防火木门是指在一定时间内能满足耐火稳定性、完整性和隔热性要求的门。主要用途在于防火,有很强的耐火力,因而选用的资料必要要有高度耐烧、耐高温,不止本身…

    防火门 2023年10月17日
    10
  • 须知的防火门基础知识

    防火门由消防部经济部指定认可实验室,根据2009年1月1日起实施的新版防火门国家标准GB_12955-2008,防火门耐火试验法测试合格,并取得经济部标准检验局核发验证登录证书及授权标识者,称之为防火门。美国NFPA及IBC规范所定义的防火门为“能够共同提供开口部一定程度的防火保护的任何防火门扇、门樘、五金及其它配件的组合。” 防火门是指在一定时间内能满足耐…

    防火门 2023年10月25日
    270

联系我们

400-800-8888

在线咨询: QQ交谈

邮件:[email protected]

工作时间:周一至周五,9:30-18:30,节假日休息

关注微信