Debugging and troubleshooting of Ruiji electric door

The following is the wiring method of the electric door

Debugging and troubleshooting of Ruiji electric door

During analog control, command: 26+27-, feedback: 22+23-, 4 and 41, 5 and 39 short circuit.

  1. This actuator has a dedicated remote setting device for setting modifications Valve parameters, the layout of the valve screen has areas I, II, and III. I area is the valve position display area, which displays the current valve position value in real time in the form of valve opening percentage. Area II is the work setting area or status alarm area, starting with the character \”F\” or \”A\”. Area III is the working parameter setting value display area or battery display area.
  2. Mode selection knob (red button) is placed In the \”stop\” position, aim the setter at the display screen, press any key on the setter (excluding the reset key), and the \”H-01\” screen will appear in area II on the display; use the down key to make the following characters appear in area II. : H01—Close direction selection(The numbers 0 (clockwise) and 1 (counterclockwise) will appear in area III of the submenu)
    H02—Remote Preferences(O (close priority), 1 (open priority) numbers will appear in area III of the submenu)
    H03—In-place control options(The numbers 0 (jog) and 1 (hold) will appear in area III of the submenu)

H04—Close limit protection option (submenuIII area will have 0 (unprotected), 1 (protected) numbers)

H05—Close over-torque protection value selection (submenuZone III will display the current valve closing torque value)

H06—Open over-torque protection value selection (submenuArea III will display the current valve opening torque value)

H07—ESD selection (0 will appear in the emergency operation III area (execution off action), 1 (perform opening action) or 2 (no action) number)

H08—Close limit point confirmation item (confirm to close limit)

H09—Open the limit point confirmation item (confirm to open the limit)

H10—Current torque display item (set whether the screen displays the torque value)

Set the above parameters through the setter

3. ​​The following is a Chinese comparison of the alarm code: (1) F-01 (Instruction error) (2) F-02 (ROM error) (3) F-03 (RAM error) (4) F-04 (A/D error) (5) F-05 (reset limit) (6) F-06 (torque overload) (7) F-07 (memory error) (8) F—08 (valve position overflow) (9) F—09 (valve position underflow) (10) F—10 (counting overflow) (11) F—11 (valve closing over-torque) (12) F—12 (Valve opening excessive torque) (13) F —13 (power supply phase loss) (14) F — 14 (motor overheating) (15) F — 15 (motor stall) 16) F — 16 (power outage) (17) F — 17 (wrong direction) (18) F— 18 (ESD closes the valve) (19) F—19 (ESD opens the valve) (20) F—20 (ESD is valid) (21) F—21 (subtraction error) (22) F—22 (addition error) ( twenty three)A-01 (Instructions are normal) (24) A-02 (ROM is normal) (25) A-03 (RAM is normal) (26) A-04 (A/D is normal)

4. The following are common faults and solutions:

1. Analysis of common fault causes of power supply phase loss and troubleshooting methods. There are two types of power supply phase loss of actuator: static phase loss and dynamic phase loss. A quick way to distinguish between these two types of phase loss is: in local mode, turn the operating button (black button) in the on or off direction. If the display immediately displays a \”power phase loss\” alarm, it is a static phase loss; if If the \”power phase loss\” alarm appears on the display after 1-2 seconds, it is a dynamic phase loss; there are differences in the cause analysis and troubleshooting methods for the two types of phase loss.

1.1 Analysis and troubleshooting of common fault causes of static phase loss Method
1.1.1 Cause analysis 1: One phase of the three-phase power supply of the actuator is missing.
Troubleshooting method 1: Use an electric pen or multimeter to measure whether the voltage on the power terminal of the actuator is normal. If not, check whether the user\’s power distribution system and lines are working normally. If there is a fault, the user needs to eliminate it to ensure that the power supply is normal.

1.1.2 Cause analysis 2: The control circuit board signal connection is unreliable.
Troubleshooting method 2: Reconnect the signal cable or replace it with a new one.

1.1.3 Cause Analysis 3: Circuit components related to the power board are damaged.
Troubleshooting method 3: Replace the power board with the same model.

1.2 Analysis and troubleshooting methods of common faults of dynamic phase loss:

1.2.1 Cause analysis 1 :Control lineThe circuit board signal connection is unreliable.

Troubleshooting method 1: Reconnect the signal cable or replace it with a new one.

1.2.2 Cause analysis 2: The AC contactor of the actuator is damaged.

Troubleshooting method 2: Replace the AC contactor with the same model.

1.2.3 Cause analysis 3: The motor of the actuator is damaged.

Troubleshooting method 3: Replace the motor with the same model.

1.2.4 Cause analysis 4: The circuit components related to the power board are damaged.

Troubleshooting method 4: Replace the power board with the same model.

2. Analysis and troubleshooting methods of common faults of motor stall2.1 Cause analysis 1: The manual/electric switching device is locked and the motor idling. Troubleshooting method 1: Use the setter to reset the actuator, turn the handwheel of the actuator, and then The electric operation actuator can be switched to electric mode and can run continuously; if it cannot be switched to electric mode, it is necessary to repeat the previous steps several times. If the fault is still not solved, please contact the manufacturer.

2.2 Cause analysis 2: The AC contactor controlling the motor is damaged or the sowing head on the main control board is loose.

Troubleshooting method 2: Replace the damaged AC contactor or re-insert the plug-in on the main control board.

3. Analysis and troubleshooting methods of common power failure causes

3.1 Cause analysis 1: The user\’s power fuse is burned out.

Troubleshooting method 1: The user checks the corresponding power distribution system and eliminates the fault.

3.2 Cause Analysis 2: Anti-wave on the power boardThe surge power fuse is damaged.

Troubleshooting method 2: Replace the anti-surge power fuse of the same model.

3.3 Cause Analysis 3: The power transformer of the actuator is damaged.

Troubleshooting method 3: Replace the power transformer with the same model if it is damaged.

3.4 Cause Analysis 4: The control circuit board signal connection is unreliable.

Troubleshooting method 4: Reconnect the signal cable or replace it with a new one.

4. Analysis and troubleshooting methods for common causes of motor overheating

4.1 Cause analysis 1: If the motor runs continuously for a long time and the temperature exceeds 130°C, the temperature switch automatically disconnects for protection.

Troubleshooting method 1: The actuator suspends work and can resume work only after the motor temperature drops.

5. Analysis and troubleshooting methods of common valve closing over-torque faults

5.1 Cause analysis 1: The actuator closing over-torque protection parameter setting is too small.

Troubleshooting method 1: Use the setter to reset the shutdown torque protection value (increase it), and perform electric operation in local mode

mechanism, so that it can run back and forth for 2 to 3 full strokes, as long as there is no over-torque alarm for closing the valve; if an alarm occurs

, continue to adjust the closing protection value until the actuator operates normally.

5.2 Cause Analysis 2: The actuator selection does not match the on-site operating conditions.

Troubleshooting method 2: Select a matching model to replace.

5.3 Cause Analysis 3: There are external factors that hinder the normal operation of the actuator (such as the valve being stuck).

Troubleshooting method 3: The user eliminates factors that affect the normal operation of the actuator.

6. Analysis and troubleshooting methods of common faults of over-torque valve opening (examples of valve closing torque)

7. Analysis and troubleshooting methods of common faults of valve overflow

7.1 Cause Analysis 1: The actuator valve position setting value is lost.
Troubleshooting method 1: Use the setter to reset the actuator and reset the upper and lower limit values ​​of the actuator.

8. Analysis and troubleshooting methods of common faults of valve underflow
8.1 Cause Analysis 1: The actuator valve position setting value is lost.
Troubleshooting method 1: Use the setter to reset the actuator and reset the upper and lower limit values ​​of the actuator.

9. Analysis and troubleshooting methods of common faults when the remote switch cannot be controlled
9.1 Cause Analysis 1 : The mode button on the actuator electrical cover is not in the remote position correctly.
Troubleshooting method 1: Align the \”remote\” character of the mode button with a pointed protrusion mark next to the knob.
9.2 Cause Analysis 2: The relevant circuit components of the knob board are damaged.
Troubleshooting method 2: Replace the knob plate.
9.3 Cause Analysis 3: The user’s remote control signal line is not wired correctly or the wiring is unreliable.
Troubleshooting method 3: Check the wiring to ensure it is correct and reliable.

10. After the actuator is powered on, the display does not showNormal fault cause analysis and troubleshooting methods
11.1 Cause analysis: Power on the actuator Reset is not normal.
Troubleshooting methods:
1) Use the setter to reset the actuator.
2) Cut off the power supply of the actuator, take out the backup battery of the actuator, wait for about 15-20 minutes and then power on again. If it is still not normal, repeat the above process several times; replace the backup battery after normal display.
3) Replace the main control board with the same model.

11. Oil leakage from the surface of the actuator oil plug
13.1 Cause analysis: The oil plug screw is loose .
Troubleshooting method: Tighten the oil plug screw and wipe the oil stain

本站内容及图片来自网络,版权归原作者所有,内容仅供读者参考,不承担相关法律责任,如有侵犯请联系我们:609448834

(0)
华夏门网的头像华夏门网
上一篇 2025年1月15日 10:46:22
下一篇 2025年1月15日 10:50:36

相关推荐

  • 电动伸缩门电动门

    电动伸缩门是一种现代化的智能安全门,具有便捷灵活、高效安全的特点。它通过电机驱动,实现门体的自动开关和伸缩功能,广泛应用于商业楼宇、大型社区、工厂企业等场所。本文将对电动伸缩门的原理、优势以及应用场景进行深入解析,带您了解其中的奥秘。 1.原理解析 电动伸缩门的工作原理主要基于电机和控制系统的协同作用。电机作为动力源,通过带动门体的伸缩装置实现门的打开和关闭…

    电动门 2023年10月18日
    690
  • 不锈钢伸缩门电动门

    不锈钢伸缩门电动门已经成为现代建筑中不可或缺的一部分。其多功能性和高效性使其在商业和住宅环境中得到了广泛的应用。 首先,不锈钢伸缩门电动门在外观上展现出了现代感和高雅感。不锈钢材质和精细的设计使得门体光滑亮丽,能够与各种建筑风格相匹配。无论是商场购物中心还是高档住宅小区,不锈钢伸缩门都能为建筑增添一份豪华和高级感。 其次,不锈钢伸缩门电动门具有高度的安全性和…

    电动门 2023年12月31日
    430
  • 电动门的设计,请各大豪华品牌都向问界M9学学

    说真的,我和屏幕前的你一样,想着这辈子都没机会拉开劳斯莱斯的马车门,然后很露怯的在车门周围摸索那个可以电动闭合的小电钮…..一想到这,我就觉得我想多了。 可是在问界M9发布会之后,我的小心思就再也没有离开问界M9的车门,于是第一时间进店好好感受了一番。作为一个技术发烧友,我也狠狠地下了一番功夫研究了下,问界M9确实在门上花了很多心思,容我慢慢道来…

    电动门 2024年1月16日
    1590
  • Modification tutorial for adding door-in-door and see-through windows to electric doors

    How to retrofit a 15-year-old electric door to add a door-in-door and a see-through window? On June 17, Kunming Haydun Automatic Doors modified a lifting door and added a door-in-d…

    电动门 2025年1月21日
    150
  • 不锈钢伸缩门,电动门价格只要658元每米

    不锈钢伸缩门,电动门价格只要658元每米 不锈钢伸缩门,电动门价格只要658元每米?!这真的不是梦想!在如今的市场上,你能够找到这样优质且经济实惠的门吗?让我们一起来看看这个事件的背后,了解这些门背后的故事和价值。 这款不锈钢伸缩门,电动门的价格实在太惊人了!除了价格之外,它还有什么其他的特点呢?这些门不仅美观,而且质量非常可靠。此外,这些门还具有防盗、隔音…

    电动门 2023年11月12日
    3010

联系我们

400-800-8888

在线咨询: QQ交谈

邮件:[email protected]

工作时间:周一至周五,9:30-18:30,节假日休息

关注微信