Part 2

1. Rotork

1. For regulating actuator (IQM type):

4~41 short, 5~39 short Connect

26+, 27-Analog signal instructions

22 +, 23-valve position feedback signal

2. As a switch type electric valve (IQ type)

4~36 short circuit

5~34 short circuit (no short circuit when there is a stop command)

Command: On: 35, 5 Off: 33, 5

Feedback: On: Level 8, 9: 6, 7

Analog current feedback: 22+, 23—

Power failure feedback: 42, 43 (normally closed)

The instructions for imported electric doors are the same, and the feedback is: 15 16

2. Autork

1. Adjustable actuator (IKM type):

4~36 short circuit 5~39 short circuit

Analog signal instructions: 26+, 27—:

Valve position feedback signal: 22+, 23—

2. For switch type electric valve (IK type)

4~36 short circuit

5~34 short circuit (if there is a stop command, stop in the middle and do not short circuit)

Commands: On: 35, 5 Off: 33, 5

Stop: 34, 5

Feedback: On: 8, 9 Off: 6, 7

SimulationAmount of current feedback: 22+, 23—

Power failure feedback: 42, 43 (normally closed)

3. Auma

1. Use as a regulating electric valve

Commands: 2+, 3— Feedback: 24+, 23—

2. Use as a switch type electric valve

Command: On: 3, 11 Off: 2, 11, Stop: 11 4

Feedback: On: 39, 40 Off: 35, 36

4. Yangzhou Siemens Integration Electric door

1. LK series

(1), as a regulating electric valve

Analog instructions: 15+, 16-

Analog feedback: 13+, 14-

(2), as a switch type electric valve

Commands: On: 18, 21 Off: 19, 21

Feedback: On: 3, 4 Off: 1, 2

Analog feedback: 13+, 14—;

(3), power supply

AC380V:22(A), 23(B), 24(C);

AC220V:23(L), ​​24(N)

2. WK series (domestic technology)

For on-off electric valves

Commands: On: 3, 4; Off: 2, 4

Stop command 1, 4

Feedback: On: 17, 18; Off: 5, 6

Analog feedback: 8+, 7— Power failure: 9 21

Self-maintaining: If X11 needs to be moved, unplug this plug

5. sipos execution agency

1. ECOTRON economical version: round plug connection with relay board (electric door)

Short circuit: 5, 6 terminals

Commands: On: 3, 1; Off: 2, 1

Emergency off: 9, 10 Stop: 4, 1

Feedback: On: 28, 29; Off: 32, 33

Analog feedback: 7+, 8—

2. PROFITRON Professional:

Round plug-in connection with relay board (adjusting door)

Analog current command: 11+, 12-

Analog feedback: 7+, 8—

3. ECOTRON Economical

Direct connection with relay board (electric door);

Divided into four terminal strips: X3: 1, X3: 2, X1, and X2

Short circuit: terminals 18 and 19 (X3: 2 terminal strip)

Command: Open: 5, 3; (X3: 1 terminal strip)

Off: 4, 3 Stop: 6, 3

Feedback: Open feedback is connected to 1 and 2; (X2 terminal strip)

Close feedback to 5 and 6

Power supply is connected to X1 terminal block L1, L2, L3

4. PROFITRON Professional

Direct connection with relay board (regulating door);

Divided into four terminal strips: X3: 1, X3: 2, X1, and X2

Short circuit: 18, 15 terminals (X3: 2 terminal strip)

Analog instructions: 14+, 15- (X3: 2 terminal strip)

Analog feedback: 1+, 2- (X3:1 terminal strip)

Feedback on: 1, 2 (X2 terminal strip)

Close feedback: 5, 6

Power failure: 17, 18 (normally closed)

6. SCHIEBEL (jog control wiring)

Short circuit: 2~3 terminals (provide power)

Commands: On: 1, 4 Off: 1, 3

Current feedback: 23 (+) 24 (—)

7. ABB tune gate

Command: 34 (+) 33 (—)

Feedback: 35 (—) 36 (+)

Short circuit: 21~15 22~16 (used to provide remote control power supply) 21+ 22—(24V power supply provided internally)

ABB electric door

Commands: On 11 12 Off 13 14

Feedback: On 7 8 Off 9 10

ABB pneumatic door

Command: 11 12 (used to supply power to the control part)

Feedback: 31 32 (requires DCS to provide 24 power supply)

8. ROTORK made in Malaysia (non-integrated)

Power: 1 2 3

Close travel switch (normally open): 8 9

Open travel switch (normally open): 17 18

Current level inverse: 32— 23+

9. QP10POO—02 (ROTORK)

Command: Off 33 34 On 34 35

Feedback: On 15 16 Off 6 7

10. 1614X90—04 (ROTORK) Tune the door

Command: 22+ 13—

Feedback: 32+ 23—

Eleven. 1410—50 ROTOCK (domestically produced in Shanghai)

Gate adjustment commands: 22+ 13—

Feedback: 32+ 23—

Electric door inching

Command: On 39 37 Off 39 38

Feedback: On 15 16 Off 8 9

If self-holding is required, short circuit: 36~39

Power failure: 41 42

Twelve. Hunan Lisheng Information Equipment Co., Ltd.

Shorting: 1~2 1~5

Power: L1 L2 L3

Command: On 2 3 Level: 2 4

Feedback: On 6 8 Off: 7 8

Torque switch: on 11 9 off 11 10

Thirteen. ABB electric pump spoon tube door adjustment

Command: 26+ 27—

Feedback: 30+ 31—

Power supply: 14+ 15—

14. Electric doors produced by Jiangsu Baiyun Electric Machinery Factory

Power: 11 12 13 (Row A)

Commands: 3+ 4—

Feedback: 5+ 6— Far and near control switching: 7 8

(7 8 short-circuit remote control)

(Row B) Feedback: On 1 2 Off 3 4

Fifteen. PS wiring

Feedback: 7+ 8—

Command: 3+ 4—

16. Chongqing Sichuan Yi Electric Door

Power supply; L1 L2 L3 PE ground

24V internal power supply 21+ 22—

Command: Off 21 13 On 21 11

Feedback: Off 9 10 On 7 8

Short circuit: 22 ~ 12 24 ~ 14 (can not short circuit)

Chongqing Sichuan Yi Door Adjustment

Short circuit: 21~15 22~16

Command: 34+ 33—

Bit inversion: 36+ 35—

Seventeen. Changzhou Lanling integrated valve wiring

Command: open 6 8 Off 6 7 Stop 6 9

Feedback: On 5 6 Level 9 10

Short circuit 2 5 for near and far control

1+ 2—used to provide 24V power supply to the control board

18. Electric pump spoon tube wiring

Power supply (110V): 1 2

Emergency command: on 6 7 off 6 8

Current command: 9+ 10—

Feedback: 11+ 12—

Nineteen. Ricky RA series electric door

Command: Off 5 33 On 5 35

Feedback: Off 6 7 On 10 11

Short circuit: 5~34 (for self-maintaining) 4~36

RQ series door adjustment

Feedback: 22+ 23—

Command: 26+ 27—

Twenty.AUMA electric door wiring (non-integrated)

Close travel switch: 9 10 (normally closed) 11 12 (normally open)

Closing torque switch: 1 2 (normally closed)

Open travel switch: 13 14 (normally closed) 15 16 (normally open)

Opening torque switch: 5 6 (normally closed)

21. Tianjin Baili SMC series wiring diagram

Command: On: 34 17 Off: 34 18 Short: 20 35

(Instructions require DC24V power supply, 22+ 23—)

Feedback: On: 24 28 Off: 26 28 Fault: 16 15

(The terminal number is based on the number on the number tube)

22. Shanghai Automation Instrument No.11 Factory 1410-50-CA (wiring diagram)

Command: On 36 37 Off 36 38 Self-maintaining: 36 39

Feedback: On 10 11 Off 8 9 Failure: 41 42

23, JORDAN American Jordan wiring

Power supply: 1 live wire 2 neutral wire Command: 3 (+) 4 (—)

Feedback: 5 (+) 6 (—)

24. Yangzhou Electric Power Equipment Repair Factory Model: 040-0.5WZ Wiring

Current feedback: 4 (+) 5 (—) Command: Off 7 9

On: 8 9 9 (Hold) DC24V: 13+ 14—

25 , German EMG wiring

Electric door: Command: On: 20 3 Off: 20 4 Stop; 20 2 Short: 21 1

Feedback: Off: 5 7 On; 5 9

Failure: 5 10

Tiaomen: Command: 22+ 24— Feedback; 23+ 24—

26. Yangzhou Electric Power Equipment Factory Model: LU—10—1

Terminals: 1 2 3 (resistor)

11 5 Open stroke torque normally closed contact

11 6 Close stroke torque normally closed contact

11 8 Open stroke torque normally open contact

11 9 Close stroke torque normally open contact

7 torque normally open common point

D1 D2 D3 Motor power supply 380V

Note: For reference only, the actual instructions shall prevail.

Part 3

1 RAGA electric door terminal block:

Open command: 5 –35

Close command: 5–33

Open feedback: 6–7

Close feedback: 10–11

Fault: 42 –43

4-36, 5-34 short circuit

2 ABB electric door terminal block:

Open command: 21 –11

Close command: 23–13

Feedback on: 7–8

Feedback off: 9 –10

Fault: 4 –5

22—12, 24—14 short circuit

3 British ROTORK electric door terminal block:

Open command: 5 –35

Close command: 5–33

Open feedback: 15–16

Close feedback: 6 –7

Fault: 24 –41

4–36 , 5-34 short circuit

4 EMG two-position electric door terminal block:

Open command: 4 –20

Off Command: 3–20

Enable feedback: 5–9

Related feedback: 5 –7

Fault: 5 –10

1–21 short circuit

5 EMG adjustable electric door terminal block:

Command: 22 –24

Feedback: 23….24

Close feedback: 5…7

Open feedback: 5…9

Fault: 5 –10

1–21 2…20 short circuit

6 Jordan adjustable electric door terminal blocks:

Commands: 3…4

Feedback: 5…6

Power: 1…2

7 AUTORK (IKM) Electric door terminal block:

Commands: 26 –27

Feedback: 22—23

Open feedback: 6—7

Close feedback: 8—9

5-39, 4-41 short circuit

8 AUTORK (IK) electric door terminal block:

Open command: 5–35

Guanzhifeed: 5—33

Feedback on: 8—9

Feedback off: 6–7

Fault: 42 –43

4-43 short circuit

9 AUTORK (IQ) electric door terminal block:

Open command: 5–35

Close command: 5—33

Open feedback: 8—9

Close feedback: 6–7

Fault: 42 –43

4—36 5—34 short circuit

10 AUTORK adjustable type

Instructions: 26 –27

Feedback: 22—23

Feedback: 6—7

Open feedback: 8—9

Fault: 4 –5

5-39, 4-41 short circuit

11 RAGA adjustable type

Command: 26 –27

Feedback: 22—23

Feedback: 6—7

Open feedback: 10–11

Fault: 4 2 –43

5—39, 4—41 short Continue

12 Shangyi Tiaomen Adjustable Type

Command: 26 –27

Feedback: 22—23

Feedback: 6—7

Open feedback: 8—9

Fault: 4 2 –43

5-39, 4-41 short circuit

13 AUMA two-position electric door terminal block:

Open command: 3 –11

Close command: 2–11

Feedback on: 39–40

Feedback off: 35 –36

Fault: 14 –15

Yangxiu valve two-position electric slow door opening:

Reference: On, 3, 4

Off, 2, 4

Feedback: On, 17, 18

Off, 5, 6

Failure, 9, 21

Far away, 10, 11: self-maintained, 19, 20:

Power supply: 220VAC, 24L, 12N

Ecott:

Refer to today: open, 3, 1

Off, 4, 1

Feedback: On , 8, 9

Off, 6, 7

Failure, 12, 13

14.15 Valve position

Far away, 10, 11: Self-maintained, 19, 20:

Part 4

1.ROTORK

1 , as an adjustable actuator (IQM type)

4-41 short circuit 5,39 short circuit

26, 27, Analog signal instructions

22, 23, valve position feedback signal

2. For switch type electric valve (IQ type)

4,36 short circuit 5,34 short circuit (if there is a stop command, do not short circuit during the stop)

Command: On: 35, 5 Off: 33, 5

Feedback: On: 8, 9 Off: 6, 7

Analog current feedback: 22, 23 ,

Power failure feedback: 42, 43 (normally closed)

二Autork

1 for regulating actuator (IKM type):

,36 short circuit 5, 39 short circuit 4

Analog signal instructions: 26, 27,

Valve position feedback signal: 22, 23,

2 switch type electric valve (IK type)

4,36 short circuit 5,34 short circuit (stop in the middle if there is a stop command) No short circuit)

Command: On: 35, 5 Off: 33, 5 Stop: 34, 5

Feedback: On: 8, 9 Off: 6, 7

Analog current feedback: 22, 23,

Power failure feedback: 42, 43 (normally closed)

3. Auma

1 for regulating electric valve

Instruction: 2,, 3, feedback: 24,, 23, 2 for on-off electric valve

Commands: On: 3, 11 Off: 2, 11 Stop: 11, 4

Feedback: On: 39, 40 Off: 35, 36

4. Yangzhou Siemens integrated electric door

1. LK series

1), as a regulating electric valve

Analog instructions: 15,, 16,

Analog feedback: 13,, 14,

2) As a switch type electric valve:

Command: On: 18, 21 Off: 19, 21

Feedback: On: 3, 4 Off: 1, 2

Analog feedback: 13, 14 ,

3) Power supply

AC380V:22(A), 23(B), 24(C)

1/4 page

AC220V:23(L), ​​24(L)

2.MK series (domestic technology)

For switch type electric valve;

19,20 short circuit

Commands: On: 3, 4 Off: 2, 4 Stop: 1, 4

Feedback: On: 17, 18 Off: 5, 6

Analog feedback: 8, 7, power failure: 9, 21

Self-maintaining: If X11 needs to be moved, unplug this plug

5. Sipos actuator

1. ECOTRON economical type: round plug-type connection with relay board(Electric door) Short circuit: 5, 6 terminals

Command: Open: 3, 1 Close: 2, 1 Emergency close: 9, 10 Stop: 4, 1 Feedback: Open: 28, 29 Off: 32, 33 Analog feedback: 7, 8,

2. PROFITRON professional type: circular plug-type connection with relay board (adjusting door)

Analog current command: 11, 12,,, 8, Analog feedback: 7

3. ECOTRON economical type: direct connection with relay board (electric door)

Divided into four terminal strips: X3:1, X3:2, X1, and X2

p>

Terminals 18 and 19 (X3: 2 terminal strip) short circuit:

Command: On: 5, 3 Off :4, 3 Stop: 6, 3 (X3:1 terminal strip)

Feedback: On: 1, 2 Off: 5, 6 (X2 terminal strip)

The power supply is connected to X1 terminal block L1, L2, L3

4. PROFITRON Professional: direct connection with relay board (adjusting door)

Divided into four terminal blocks: X3:1, X3:2, X1, and X2

Short-circuit: 18, 15 terminals ( X3: 2 terminal strip)

Analog instructions: 14, 15, (X3: 2 terminal strip)

Analog feedback: 1,, 2, (X3: 1 terminal strip)

p>

Open feedback: 1, 2 (X2 endsub-row)

Close feedback: 5, 6

Power failure: 17, 18 (normally closed)

Six (SCHIEBEL (jog control wiring)

Short circuit: terminals 2 and 3 (provide power)

Command: On: 1, 4 Off: 1, 3

Current feedback: 23,, 24,

Seven (ABB Adjustment Gate

Command: 34,, 33,

Feedback: 35,, 36,

Short-circuit: 21,15, 22,16 (used to provide Remote control power supply)

21,, 22, (24v power supply provided internally)

ABB electric door

Command: open 11, 12, close 13, 14

Page 2/4

Feedback: On 7, 8, Off 9, 10

ABB pneumatic door

Instructions: 11, 12 (used to supply power to the control part)

Feedback: 31, 32 (requires DCS to provide 24v power supply)

Eight (Malaysian ROTORK (not one-piece) )

Power: 1, 2, 3

Close travel switch (normally open): 8, 9

Open travel switch (normally open): 17, 18

Current bit inversion: 32, 23,

Nine(QP10POO,02(ROTORK)

Command: Off 33, 34, On 34, 35

Feedback: On 15, 16, Off 6, 7

Ten (1614X90-04(ROTORK) door adjustment

,, 13, command: 22

Feedback: 32,, 23,

November, 1410,50 RORORK (Made in Shanghai)

Gate adjustment instructions: 22+, 13,

Feedback: 32,, 23,

Electric door jog

Command: open 39, 37, close 39, 38

Feedback: On 15, 16, Off 8, 9

If self-holding is required, short-circuit: 36,39

Power failure: 41, 42

Twelve, Hunan Lisheng Information Equipment Co., Ltd.

Short: 1,2, 1,5

Power supply: L1 L2 L3

Command: On 2, 3 Off 2, 4

Feedback: On 6, 8, Off 7, 8

Torque switch: on 11, 9, off 11, 10

Thirteen, ABB electric pump spoon tube door adjustment

Instructions: 26,, 27,

Feedback: 30,, 31,

Power: 14,, 15,

Fourteen, electric door produced by Jiangsu Baiyun Electric Machinery Factory

Power supply: 11, 12, 13 (row A)

Command: 3,, 4,

Feedback: 5,, 6, far and near control switching: 7, 8 (7, 8 short for remote control)

Page 3/4

B row feedback: On 1, 2, Off 3, 4

Fifteen, PS wiring

Feedback: 7,, 8,

Instructions: 3,, 4,

Sixteen, Chongqing Sichuan Electric Electric Door

Power supply: L1 L2 L3 PE ground

24V internal power supply: 21,, 22,

Command: Off 21, 13, On 21, 11

Feedback: Off 9, 10, On 7, 8

Short-circuit: 22, 12, 24, 14 (can it not be short-circuited)

Chongqing Sichuan Yi Adjusting Door

Short connections: 21,15, 22 ,16

Command: 34,, 33,

Bit inversion: 36,, 35,

Seventeen, Changzhou Lanling integrated valve wiring

Command: open 6, 8, close 6, 7, stop 6, 9

Feedback: Open 5, 6 Off 9, 10

2,5 is used for near and far control short circuit:

1, 2, used to provide 24V power supply for the control board

Eighteen, electric pump spoon tube wiring

Power supply (110V): 1, 2

Emergency command: open 6, 7, close 6, 8

Current command: 9,, 10,

p>

Feedback: 11, , 12,

Nineteen, Ruiji RA series electric door

Command: off 5, 33, on 5, 35

Feedback: Off 6, 7, On 10, 11

Short: 5,34 (for self-holding) 4,36

RO series

Feedback: 22,, 23,

Instructions: 26,, 27,

Twenty, AUMA electric door wiring (non-integrated)

Close travel switch: 9, 10 (normally closed) 11, 12 (normally open)

Close torque switch: 1, 2

Open travel switch: 13, 14( Normally closed) 15, 16 (normally open)

Open torque switch: 5, 6 (normally closed)

(for production examination only, subject to the book of the executing agency)

Disclaimer: The content published on this platform is marked as original. . Reposted and shared contentThe content is for learning purposes only and is for reference only and does not represent my own views and positions. If there is any infringement, please contact us to delete it. Welcome all colleagues to communicate and learn together!

本站内容及图片来自网络,版权归原作者所有,内容仅供读者参考,不承担相关法律责任,如有侵犯请联系我们:609448834

Like (0)
华夏门网的头像华夏门网
Previous 2024年12月25日
Next 2024年12月25日

相关推荐

  • 小米SU7又一強敵!極越07量產下線!電動門+升降尾翼+8295芯片,爆款預定…

    8月16日,極越汽車旗下的第二款車型——極越07(詢底價|查參配)量產車正式下線,該車此前相繼公佈外觀和內飾,預計在8月30日開幕的成都車展開啟預售。極越07定位中大型純電轎車,基於SEA浩瀚架構打造而來,搭載8295芯片和高階智駕系統,將於年內上市。 外觀方面,極越07前臉和尾部設計與極越01較為相似,均采用貫穿式大燈設計,呈現出較強的科技感。同時,前大燈…

    电动门 2024年9月13日
    70
  • 小米SU7升級電動門,外加幾個實用的項目,隻需要一萬塊

    說說小米蘇 7 的升級方案! 1. 今天帶大傢來看一臺小米蘇 7,車主一買就拿到我們這兒來升級隱形車衣、車窗膜以及腳墊軟包,這次再過來升價兩個非常實用也非常有逼格的電子方面的升級方案。電動機蓋以及四個門的電吸門是無損安裝,不得破壞原車線路,並且是在屏幕控制,非常方便。 2. 這臺車子最先升級的軟磨座墊是黑色納帕皮,並且是雙層可拆卸,1000 多塊錢。車窗膜由…

    电动门 2024年11月10日
    40
  • 理想7、8、9 4门电动门 对标劳斯莱斯 高端大气上档次[强]

    理想7、8、9,4门电动门对标劳斯莱斯,高端大气上档次。 理想车主们,现在广东瑞宁电动门公司出了理想电动门,大家可以过来看一下。现在电动门有九大功能。 ·第一个功能就是轻松便捷拉起的开。 ·第二个功能就是上车之后脚踩刹车的关闭。 ·第三个功能就是内门把手的轻触开,再拉关闭。 ·第四个功能就是轻触关闭。 ·第五个功能就是智能防碰。假如边上有人或者有车,一打开它…

    电动门 2024年5月31日
    280
  • 业主强行通过小区电动门受伤,起诉物业公司被法院驳回

    新京报讯(记者 张静姝 通讯员 王辉)小区电动门缓缓关闭时,业主王女士骑着电动自行车加速,想从夹缝中穿过去,结果发生意外受伤,王女士起诉物业公司要求赔偿。近日,北京市房山区人民法院审理了该案,最终,法院未支持王女士的诉求。 新京报记者了解到,王女士所住小区门口的人行通道设置了电动门。刷门禁卡或按开门按钮,大门会自动打开,然后自行关闭。2023年12月24日下…

    电动门 2024年3月28日
    50
  • 转载–auma电动门原理及接线图

    来源:热控圈 auma电动门接线图

    电动门 2024年1月25日
    3030

联系我们

400-800-8888

在线咨询: QQ交谈

邮件:[email protected]

工作时间:周一至周五,9:30-18:30,节假日休息

关注微信