Reprinted–Debugging and common troubleshooting of Yangxiu electric doors

Source: Thermal Control Circle

Debugging method and troubleshooting of Yangxiu electric door

1. Yangxiu DZW series electric actuator

1.1 Main technical parameters

Power supply: AC380V, 50Hz, three-phase three-wire system

Valve position signal: output 4~20mA

Protection level: IP55

Ambient temperature: -20℃~60℃

Output Power: 0.030~15KW

1.2 Operation

operate in the \”remote\” or \”local\” state respectively. When the power is turned on each time, it is in \”remote\”. If you need to perform \”local\” operation, click \”local\” ” button to switch the “Remote” status to “Present” \”Local\” state. At this time, the green luminous tube indicating the \”remote\” state goes out, and the red luminous tube indicating the \”local\” state lights up. The \”on\”, \”off\” and \”stop\” buttons for remote operations do not work and can only be operated in Operate the \”on\”, \”off\” and \”stop\” buttons on the local operation panel.

1.3 Precautions for adjustment

Check whether the grounding is reliable before turning on the power. Newly installed electric devices must be powered on for the first time. Check the motor phase sequence and whether the control circuit is correct to prevent the motor from running out of control.

1.4 Torque control mechanism adjustment

1.4.1 First adjust the closing torque.

1.4.2 According to the torque characteristic curve provided by the product, start from the small torque characteristic curve and the small torque value, and gradually increase the torque value until the valve is tightly closed. .

1.4.3 Adjust the torque. Generally, the torque in the opening direction is larger than the torque in the closing direction.

1.4.4 The above adjustments are all in the blankIt should be adjusted when there is no medium pressure and other factors. When there is pressure and temperature, attention should be paid to whether it can be closed tightly. If it is not closed tightly, it should be increased appropriately. The torque value shall be based on whether it is closed tightly or opened.

1.5 Stroke control mechanism adjustment

1.5.1 Close the valve tightly manually.

1.5.2 To disengage the stroke control mechanism, use a screwdriver to push the push rod of the stroke control mechanism and rotate it 90° to disengage the driving pinion from the counter gear set.

1.5.3 Use a screwdriver to rotate the \”close\” adjustment shaft in the direction of the arrow until the cam presses the spring pressure plate and causes the micro switch to operate. Then the close stroke is initially adjusted.

1.5.4 Loosen the ejector pin to ensure that the driving gear meshes correctly with the gears on both sides. To ensure the correct meshing, after loosening the ejector pin, you must use a screwdriver to Turn the adjustment shaft left or right.

1.5.5 Opening direction adjustment: After adjusting the closing direction, open the valve to the required position by hand, then disengage the stroke control mechanism and turn \”open\” Turn the adjustment shaft toward the arrow and rotate it in the direction of the arrow until the cam presses the spring plate and activates the micro switch. Then mesh the travel mechanism with the driving gear to complete the adjustment of the open direction stroke. You can repeat the above steps for adjustment.

2. Common fault handling

2.1 Analysis and troubleshooting methods of common faults of power phase loss

Actuator power supply phase loss is divided into two types: static phase loss and dynamic phase loss. A quick way to distinguish between these two types of phase loss is: in local mode, turn the operating button (black button) in the on or off direction. If the display immediately displays a \”power phase loss\” alarm, it is a static phase loss; if If the \”power phase loss\” alarm appears on the display after 1-2 seconds, it is a dynamic phase loss; there are differences in the cause analysis and troubleshooting methods for the two types of phase loss.
2.1.1 Cause analysis and troubleshooting methods for common faults of static phase loss
(1) Cause analysis: One phase of the three-phase power supply of the actuator is missing.
Troubleshooting method: Use an electric pen or multimeter to measure whether the voltage on the power terminal of the actuator is normal. If not, check whether the user\’s power distribution system and lines are working normally. If there is a fault, the user needs to eliminate it to ensure that the power supply is normal.
(2) Cause analysis: The control circuit board signal connection is unreliable.
Troubleshooting method: Reconnect the signal cable or replace it with a new one.

(3) Cause analysis: The circuit components related to the power board are damaged.
Troubleshooting method: Replace the power board with the same model.

2.1.2 Analysis and troubleshooting methods of common faults of dynamic phase loss
(1) Cause analysis: The control circuit board signal connection contact is unreliable.
Troubleshooting method: Reconnect the signal cable or replace it with a new one.

(2) Cause analysis: The AC contactor of the actuator is damaged.
Troubleshooting method: Replace the AC contactor with the same model.

(3) Cause analysis: The motor of the actuator is damaged.
Troubleshooting method: Replace the motor with the same model.

(4) Cause analysis: The circuit components related to the power board are damaged.

Troubleshooting method: Replace the power board with the same model.

2.2 Cause analysis and troubleshooting methods for common motor stall failures
(1) Cause analysis: The manual/electric switching device is locked and the motor is idling.
Troubleshooting method: Use the setter to reset the actuator, turn the handwheel of the actuator, and then electrically operate the actuator to switch to electric mode and run continuously; if it fails to switch to electric mode, it needs to be repeated multiple times. If the fault still cannot be solved after following the previous steps, please contact the factory.

(2) Cause analysis: The AC contactor controlling the motor is damaged or the sow head on the main control board is loose.
Troubleshooting method: Replace the damaged AC contactor or re-insert the plug-in on the main control board.

2.3 Analysis and troubleshooting methods of common power failure causes
(1) Cause analysis: The user\’s power fuse is burned out.
Troubleshooting method: The user checks the corresponding power distribution system and eliminates the fault.
(2) Cause analysis: The anti-surge power fuse on the power board is damaged.
Troubleshooting method: Replace the anti-surge power supply fuse of the same model.
(3) Cause analysis: The power transformer of the actuator is damaged.
Troubleshooting method: Replace the power transformer with the same model if it is damaged.
(4) Cause analysis: The control circuit board signal connection is unreliable.
Troubleshooting method: Reconnect the signal cable or replace it with a new one.

2.4 Analysis and troubleshooting methods of common faults of motor overheating
(1) Cause analysis: The motor runs continuously for a long time and the temperature exceeds 130℃, the temperature switch automatically disconnects the protection .
Troubleshooting method: The actuator suspends work and can resume work only after the temperature of the motor drops.

2.5 Cause analysis and troubleshooting methods for common valve closing over-torque faults
(1) Cause analysis: Actuator closing over-torque protection parameter settingThe setting is too small.
Troubleshooting method: Use the setter to reset the closing torque protection value (increase it), operate the actuator electrically in local mode, and make it run back and forth for 2 to 3 full strokes, without the valve closing over-torque alarm occurring. Yes; if an alarm occurs, continue to adjust the shutdown protection value until the actuator operates normally.
(2) Cause analysis: The actuator selection does not match the on-site operating conditions.
Troubleshooting method: Choose a matching model to replace.
(3) Cause analysis: There are external factors that hinder the normal operation of the actuator (such as the valve being stuck).
Troubleshooting method: The user eliminates factors that affect the normal operation of the actuator.

2.6 Analysis and troubleshooting methods of common faults of over-torque valve opening (example with closing torque valve)

2.7 Valve position Analysis and troubleshooting methods of common overflow faults
(1) Cause analysis: The actuator valve position setting value is lost.
Troubleshooting method: Use the setter to reset the actuator and reset the upper and lower limit values ​​of the actuator.

2.8 Analysis and troubleshooting methods of common failures of valve position underflow
(1) Cause analysis: The actuator valve position setting value is lost.
Troubleshooting method: Use the setter to reset the actuator and reset the upper and lower limit values ​​of the actuator.

2.9 Analysis and troubleshooting methods of common faults when the remote switch cannot be controlled
(1) Cause analysis: The mode button on the electrical cover of the actuator is not in the correct remote position.
Troubleshooting method: Align the \”remote\” character of the mode button with a pointed protrusion mark next to the knob.
(2) Cause analysis: The relevant circuit components of the knob plate are damaged.
Troubleshooting: Replace the knob plate.
(3) Cause analysis: The user\’s remote control signal line is not wired correctly or the wiring is unreliable.
Troubleshooting method: Check the wiring to ensure it is correct and reliable.

2.10 Cause analysis and troubleshooting methods for abnormal display on the display screen after the actuator is powered on
(1) Cause analysis: The actuator resets abnormally after power on.
Troubleshooting method: a Use the setter to reset the actuator. b Cut off the power supply of the actuator, take out the backup battery of the actuator, wait for about 15-20 minutes and then power it on again. If it is still not normal, repeat the above process several times; replace the backup battery after normal display. cReplace the main control board with the same model.

2.11 Oil leaks from the surface of the actuator oil plug
(1) Cause analysis: The oil plug screw is loose.
Troubleshooting method: Tighten the oil plug screw and wipe away the oil stains.

本站内容及图片来自网络,版权归原作者所有,内容仅供读者参考,不承担相关法律责任,如有侵犯请联系我们:609448834

(0)
华夏门网's avatar华夏门网
上一篇 2024年12月19日 10:48:41
下一篇 2024年12月19日 10:55:08

相关推荐

  • Reprint–Several common faults and solutions for electric doors

    Source: Zhu Hongming Zhongtian Iron and Steel Thermal Power Plant Electric doors are common equipment in industrial systems. They cooperate with DCS and PLC and are easy and flexib…

    电动门 2024年12月15日
    100
  • 豪華MPV新標桿!車長達5346mm,配備雙側電動門,僅售不到20萬

    導讀 大眾威然的後排座椅佈局可是讓人眼前一亮,2+2+3的設計,不僅能滿足傢庭出行的需求,還能兼顧商務接待的場合。想知道它在空間和舒適性上到底有多出色?繼續往下看,帶你深入瞭解這款MPV的魅力所在! 大眾威排座椅佈局與空間 在車內空間方面,大眾威然可謂下足瞭功夫。後排座椅佈局為2+2+3,第二排座椅為獨立商務座椅,第三排座椅為常規座椅,雖然第三排座椅寬度與第…

    电动门 2024年11月22日
    120
  • 南寧電動門,電動門安裝廠傢就是北通門業

    南寧電動門,電動門安裝廠傢就是北通門業 大傢好,今天我要和大傢分享一個關於南寧電動門的故事。你們知道嗎,南寧最近有一傢很不錯的電動門安裝廠傢,叫做北通門業。他們提供瞭各種不同類型的電動門,包括普通的電動門、防盜電動門、自動感應門等等。這些門不僅外觀時尚,而且非常安全實用。 北通門業的電動門安裝團隊非常專業,他們可以為你提供快速、高效的安裝服務。如果你有任何問…

    电动门 2024年8月18日
    90
  • 安裝電動門之前,業主需提前做哪些準備工作?

    安裝電動門之前,業主需提前做哪些準備工作? 伊頓莊園一客戶五月份在海頓車庫門展廳看樣確認,簽約一樘雙車位的翻板車庫門訂單,支付瞭5000元預付款(定金),過完中秋節,聯系工作人員表示希望10月國慶節之前能幫忙安裝好,國慶節的時候不方便施工。然後海頓車庫門同事上門服務,對接復核尺寸、下單生產和安裝。這期間,業主在裝修過程中,需要對車庫的門洞、墻面、地面做好哪些…

    电动门 2024年10月1日
    200
  • 標配都是頭等艙!電動門+混動引擎,2022年這5款MPV還能繼續火?

    在整個2021年,迎來瞭豪華MPV熱度期,眾多的主流品牌和新生代MPV紛紛到來,而2021年即將結束,全新的2022年即將到來,而在2021年很多MPV車型展現出瞭自身的實力和競爭力,包括廣汽豐田賽那,起亞嘉華,東風風行M7,本田奧德賽,大眾邁特威這5款車型,標配頭等艙佈局,同時匹配瞭電動門,豐田賽那和本田奧德賽還匹配瞭混合動力系統,整體的競爭力和實力表現的…

    电动门 2024年8月31日
    470

联系我们

400-800-8888

在线咨询: QQ交谈

邮件:[email protected]

工作时间:周一至周五,9:30-18:30,节假日休息

关注微信